This guide is applicable to the DCL Ultra-Small Series actuators, with the following models:

  • DCL-02A

  • DCL-02B

  • DCL-02G

华易精巧系列执行器 DCL-02 配阀 | DCL-02 Actuator Valve

Common Faults and Troubleshooting Methods

 

결함Possible Causes문제 해결 방법
Actuator does not open or close on initial start1. 잘못된 배선Check the wiring according to the actuator’s wiring diagram.
 2. 잘못된 전원 공급 장치Ensure the power supply voltage is within ±10% of the actuator’s rated voltage and the current is 3 times the rated current.
 3. Faulty control switch or relayMeasure the input voltage at the actuator’s control terminal using a multimeter to verify it matches expectations.
 4. Control system mismatchTest the actuator with a mechanical switch. If it operates normally, verify the control system’s output logic.
 5. Multiple actuators or actuators and other devices connected in parallelSwitch actuators should use single-path control and not be wired in parallel, as this affects the startup capacitor.
Actuator can only open or close1. 잘못된 배선Check the wiring using the actuator’s wiring diagram.
 2. Incorrect full open/close cam settingRefer to the “How to Set Electric Switch-Type Valves” guide and correctly set the cam positions.
Actuator stops in the middle of travel1. Valve jammedCheck for blockages in the valve. Clear any obstruction and retry after the actuator’s overload protection cools.
 2. Solid material in fluid causing valve jamInspect the fluid for solid particles causing valve jams. Clear the jam and retry after the actuator’s overload protection cools.
 3. Incorrect full open/close stopper settingRefer to the “How to Set Electric Switch-Type Valves” guide and correctly adjust the stopper positions.
Unable to turn actuator using the handle1. Solid material in fluid causing valve to seizeCheck for blockage in the valve. Clear the blockage and retry after the actuator’s overload protection cools.
 2. Valve seizingInspect the valve for jamming. Clear the blockage and retry after the actuator’s overload protection cools.
 3. Damaged actuator reduction mechanismRemove the actuator from the valve and rotate the handle. If it doesn’t move, replace the actuator.
No position feedback signal1. Incorrect wiring at the switchCheck the wiring according to the actuator’s wiring diagram.
 2. Incorrect full open/close cam settingRefer to the “How to Set Electric Switch-Type Valves” guide and set the cam position correctly.
 3. Overcurrent causing position feedback switch damage1. Check if the full open/close cam is pressing on the position feedback switch correctly, as per the guide.
  2. Measure if the position feedback circuit is closed.

 

Verify that the operating conditions meet the parameter requirements.

Electric actuators may fail due to improper use or being used in incorrect operating conditions. When used within the operating conditions defined in the product specifications, the actuator can be expected to operate reliably for an extended period without failure.

  • Supply Voltage: The voltage from the power supply must be within the rated operating voltage range of the actuator. Overvoltage or undervoltage may shorten the actuator’s lifespan.

  • Supply Current: The starting current of the motor is significantly higher than the rated current. To ensure reliable operation, use a power supply capable of delivering at least 3 times the rated current of the actuator.

  • Temperature: Ensure the actuator operates within its rated temperature range. Using the actuator outside this range may result in poor performance, reduced lifespan, and eventual failure.

  • Environment: The DCL switch-type actuator has an IP67 weatherproof rating, making it suitable for both indoor and outdoor applications. It offers a degree of protection against rain and splashing water, helping to prolong the actuator’s life by shielding it from rain, snow, ice, and UV (sunlight). However, in highly corrosive environments, electronic components may fail prematurely. Non-explosion-proof actuators should not be used in explosive environments.

  • Duty Cycle: The DCL switch-type actuator has a duty cycle of 70% (42 seconds of operation per minute, followed by 18 seconds of rest). Exceeding this duty cycle may cause the motor to enter thermal protection.

Check the Wiring of the Actuator

Ensure the actuator is wired correctly according to the wiring diagram provided by the manufacturer. Follow these steps to verify the wiring:

  1. Power Supply:

    • Check the power supply connections to ensure they match the actuator’s required input voltage and current.

  2. Control Connections:

    • Verify that the input and output control connections are securely attached and in the correct configuration as per the actuator’s wiring diagram.

  3. Signal Wiring:

    • Check the wiring for control signals, such as 4-20mA or 0-10V, depending on the actuator’s specifications.

    • Confirm that there are no loose connections or short circuits.

  4. Grounding:

    • Ensure that the actuator is properly grounded to prevent electrical interference or damage.

  5. Connections to Other Equipment:

    • If the actuator is connected to other devices, make sure those connections are also correct and do not cause interference or power issues.

If the wiring appears correct, but the actuator is still malfunctioning, further troubleshooting or assistance from a technician may be necessary.

A - 2개의 활성 엔드 포지션 신호 출력 포함

DCL 华易执行器A型接口图
  • K로 액추에이터를 제어하여 열거나 닫습니다.
  • 종단 위치 OPEN/CLOSE의 출력 단자는 종단 위치에 도달하면 220VAC 활성 신호 형태로 이벤트를 전송합니다.

 

세부 정보 연결:

  1. AC85-220V 공급 전원 중립을 P1에 연결합니다.
  2. AC85-220V 라인을 CLOSE(P2)로 전환하여 밸브를 닫습니다.
  3. AC85-220V 라인을 OPEN(P3)으로 전환하여 밸브를 엽니다.
  4. P5는 액추에이터가 열림의 끝 위치에 도달했을 때 표시등을 구동하는 데 사용할 수 있는 AC220V 소스를 출력하는 끝 위치 OPEN 단자입니다.
  5. P6은 액추에이터가 닫힘의 끝 위치에 도달했을 때 표시등을 구동하는 데 사용할 수 있는 AC220V 소스를 출력하는 끝 위치 OPEN 단자입니다.
  6. 접지를 P7에 연결합니다.

B - 패시브 엔드 포지션 스위치 2개 포함

DCL 华易执行器B型接口图
  • K로 액추에이터를 제어하여 열거나 닫습니다.
  • 엔드 포지션 OPEN/CLOSE의 출력 단자는 엔드 포지션에 도달하면 수동 신호 형태로 이벤트를 전송합니다.

 

세부 정보 연결:

  1. AC85-220V 공급 전원 중립을 P1에 연결합니다.
  2. AC85-220V 라인을 CLOSE(P2)로 전환하여 밸브를 닫습니다.
  3. AC85-220V 라인을 OPEN(P3)으로 전환하여 밸브를 엽니다.
  4. P4는 일반적으로 신호 GND에 연결되는 종단 위치 OPEN/CLOSE의 패시브 접점 신호용 COM입니다.
  5. P5는 액추에이터가 열림의 끝 위치에 도달하면 COM에 연결되는 끝 위치 열림 단자입니다.
  6. P6은 액추에이터가 닫힘의 끝 위치에 도달하면 COM에 연결되는 끝 위치 닫힘 단자입니다.
  7. 접지를 P7에 연결합니다.

G - 종단 위치 스위치가 2개인 DC 모터

DCL 华易执行器G型接口图
  • 단자 1과 2 사이의 공급 전원 방향에 따라 액추에이터를 열거나 닫도록 제어합니다.
  • 엔드 포지션 OPEN/CLOSE의 출력 단자는 엔드 포지션에 도달하면 수동 신호 형태로 이벤트를 전송합니다.

 

세부 정보 연결:

  1. DC24V+를 P1에, DC24V-를 P2에 연결하여 밸브를 닫습니다.
  2. DC24V+를 P2에, DC24V-를 P1에 연결하여 밸브를 닫습니다.
  3. P3은 일반적으로 신호 GND에 연결되는 종단 위치 OPEN/CLOSE의 패시브 접점 신호용 COM입니다.
  4. P4는 액추에이터가 열림의 끝 위치에 도달하면 COM에 연결되는 끝 위치 열림 단자입니다.
  5. P5는 액추에이터가 닫힘의 끝 위치에 도달하면 COM에 연결되는 끝 위치 CLOSE 단자입니다.
  6. 접지를 P7에 연결합니다.

참고: 참고

  • 점선 상자 안의 회로는 액추에이터의 내부 회로입니다. 외부 회로는 액추에이터 사용을 위한 전기 연결 데모입니다.
  • 회로 연결에 대한 기타 구체적인 요구 사항이 있는 경우 언제든지 기술 지원팀에 문의하시기 바랍니다. 

When conducting troubleshooting on-site, feel free to contact our technical service personnel immediately for assistance in diagnosing and resolving the issue.
Contact phone number: 13026331611 (Mr. Chen)