{"id":6033,"date":"2023-08-03T20:44:54","date_gmt":"2023-08-03T12:44:54","guid":{"rendered":"https:\/\/www.dcl-controls.com\/?p=6033"},"modified":"2025-04-18T11:35:31","modified_gmt":"2025-04-18T03:35:31","slug":"dcl-02-switch","status":"publish","type":"post","link":"https:\/\/www.dcl-controls.com\/nl_nl\/support\/mr-actuator\/dcl-02-switch","title":{"rendered":"Voorkomende storingen en het oplossen van problemen van DCL-02 schakelactor"},"content":{"rendered":"<div data-elementor-type=\"wp-post\" data-elementor-id=\"6033\" class=\"elementor elementor-6033\" data-elementor-post-type=\"post\">\n\t\t\t\t\t\t<section class=\"elementor-section elementor-top-section elementor-element elementor-element-d1ba3c2 elementor-section-full_width elementor-section-height-default elementor-section-height-default\" data-id=\"d1ba3c2\" data-element_type=\"section\">\n\t\t\t\t\t\t<div class=\"elementor-container elementor-column-gap-default\">\n\t\t\t\t\t<div class=\"elementor-column elementor-col-100 elementor-top-column elementor-element elementor-element-13d9a9c\" data-id=\"13d9a9c\" data-element_type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-d791082 elementor-widget elementor-widget-text-editor\" data-id=\"d791082\" data-element_type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p>Deze wizard is geschikt voor DCL ultra-kleine serie aandrijvingen, de modellen zijn als volgt\uff1a<\/p><ul><li>DCL-02A \/ DCL-02B \/ DCL-02G -<\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-cb92161 elementor-widget elementor-widget-image\" data-id=\"cb92161\" data-element_type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img fetchpriority=\"high\" decoding=\"async\" width=\"176\" height=\"399\" src=\"https:\/\/www.dcl-controls.com\/content\/dam\/actuator\/images\/shelf-banner\/dcl-02-valve.webp\" class=\"attachment-full size-full wp-image-4861\" alt=\"\u534e\u6613\u7cbe\u5de7\u7cfb\u5217\u6267\u884c\u5668 DCL-02 \u914d\u9600 | DCL-02 Actuator Valve\" srcset=\"https:\/\/www.dcl-controls.com\/content\/dam\/actuator\/images\/shelf-banner\/dcl-02-valve.webp 176w, https:\/\/www.dcl-controls.com\/content\/dam\/actuator\/images\/shelf-banner\/dcl-02-valve-132x300.webp 132w, https:\/\/www.dcl-controls.com\/content\/dam\/actuator\/images\/shelf-banner\/dcl-02-valve-5x12.webp 5w\" sizes=\"(max-width: 176px) 100vw, 176px\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-e8500e7 elementor-widget elementor-widget-heading\" data-id=\"e8500e7\" data-element_type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<h2 class=\"elementor-heading-title elementor-size-default\">1. Voorkomende storingen en het oplossen van problemen methoden.<\/h2>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-4741093 elementor-widget elementor-widget-shortcode\" data-id=\"4741093\" data-element_type=\"widget\" data-widget_type=\"shortcode.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t<div class=\"elementor-shortcode\">\n<table id=\"tablepress-35\" class=\"tablepress tablepress-id-35 tbody-has-connected-cells\">\n<thead>\n<tr class=\"row-1\">\n\t<th class=\"column-1\">fout<\/th><th class=\"column-2\">Mogelijke oorzaak<\/th><th class=\"column-3\">Uitsluiting methode<\/th>\n<\/tr>\n<\/thead>\n<tbody class=\"row-striping row-hover\">\n<tr class=\"row-2\">\n\t<td rowspan=\"5\" class=\"column-1\">De actor zal niet in-of uitschakelen wanneer het voor het eerst wordt gestart<\/td><td class=\"column-2\">1. Onjuiste bedrading<\/td><td class=\"column-3\">Controleer of de bedrading correct is volgens het schakelschema van de actor?<\/td>\n<\/tr>\n<tr class=\"row-3\">\n\t<td class=\"column-2\">2. Onjuiste voeding<\/td><td class=\"column-3\">Bevestigen dat de uitgangsspanning van de voeding is \u00b110% van de nominale stroom van de aandrijving, en de uitgangsstroom is 3 keer de nominale stroom van de aandrijving.<\/td>\n<\/tr>\n<tr class=\"row-4\">\n\t<td class=\"column-2\">3. Abnormale control schakelaar of besturing relais<\/td><td class=\"column-3\">Gebruik een multimeter voor het meten van de ingangsspanning op de bedieningsaansluiting van de actuator schakelaar om na te gaan of het voldoet aan de verwachtingen?<\/td>\n<\/tr>\n<tr class=\"row-5\">\n\t<td class=\"column-2\">4. Controle systeem van matching probleem<\/td><td class=\"column-3\">Gebruik een mechanische schakelaar voor het meten van de functie van de aandrijving. Indien de aandrijving werkt, controleer of de uitgang van de logica van de besturing voldoet aan de verwachtingen?<\/td>\n<\/tr>\n<tr class=\"row-6\">\n\t<td class=\"column-2\">5. Meerdere actoren of aandrijvingen parallel met andere apparatuur<\/td><td class=\"column-3\">De schakelactor is gestart door middel van het starten van de condensator, en het vergelijken met andere apparatuur een impact zal hebben op de capaciteit waarde van de start van de condensator. Daarom is de schakelactor kan alleen gebruik maken van een interne controle, in plaats van parallel.<\/td>\n<\/tr>\n<tr class=\"row-7\">\n\t<td rowspan=\"2\" class=\"column-1\">De aandrijving kan alleen worden in-of uitgeschakeld<\/td><td class=\"column-2\">1. Onjuiste bedrading<\/td><td class=\"column-3\">1. Gebruik een mechanische schakelaar voor het meten van de functie van de aandrijving. Indien de aandrijving werkt, controleer of de uitgang van de logica van de besturing voldoet aan de verwachtingen?<br \/>\n2. Controleer of de bedrading correct is volgens het schakelschema van de actor?<br \/>\n<\/td>\n<\/tr>\n<tr class=\"row-8\">\n\t<td class=\"column-2\">2. Onjuiste instelling van de volledig op\/fullyoff cam<\/td><td class=\"column-3\">verwijzing<a href=\"\/nl_nl\/faq\/actuator\/set-up-dcl-valve\/\">&#034;Het instellen van een switch-type Elektrische klep&#034;<\/a>Stel de cam positie terecht.<\/td>\n<\/tr>\n<tr class=\"row-9\">\n\t<td rowspan=\"3\" class=\"column-1\">De aandrijving stopt in het midden van de reis<\/td><td class=\"column-2\">1. Afsluiter stagnatie<\/td><td class=\"column-3\">Controleer of de klep vast te zitten, te elimineren van het vast zit, en probeer het opnieuw nadat de motor wordt gekoeld door overbelasting bescherming.<\/td>\n<\/tr>\n<tr class=\"row-10\">\n\t<td class=\"column-2\">2. Potenti\u00eble vaste stoffen in de vloeistof medium dat de klep te stagneren.<\/td><td class=\"column-3\">Controleer of er zijn vaste stoffen vast te zitten in het vloeibaar medium, het elimineren van de klep vast zit, en probeer het opnieuw nadat de motor wordt gekoeld door overbelasting bescherming.<\/td>\n<\/tr>\n<tr class=\"row-11\">\n\t<td class=\"column-2\">3. Onjuiste instelling van volledig aan\/volledig uit stopper<\/td><td class=\"column-3\">verwijzing<a href=\"\/nl_nl\/faq\/actuator\/set-up-dcl-valve\/\">&#034;Het instellen van een switch-type Elektrische klep&#034;<\/a>Stel de stop positie terecht.<\/td>\n<\/tr>\n<tr class=\"row-12\">\n\t<td rowspan=\"3\" class=\"column-1\">Met behulp van de handgreep, de aandrijving kan niet worden geroteerd<\/td><td class=\"column-2\">1. Potenti\u00eble vaste stoffen in de vloeistof medium dat de klep vast komen te zitten.<\/td><td class=\"column-3\">Controleer of er zijn vaste stoffen vast te zitten in het vloeibaar medium, het elimineren van de klep vast zit, en probeer het opnieuw nadat de motor wordt gekoeld door overbelasting bescherming.<\/td>\n<\/tr>\n<tr class=\"row-13\">\n\t<td class=\"column-2\">2. Klep vast<\/td><td class=\"column-3\">Controleer of de klep vast te zitten, te elimineren van het vast zit, en probeer het opnieuw nadat de motor wordt gekoeld door overbelasting bescherming.<\/td>\n<\/tr>\n<tr class=\"row-14\">\n\t<td class=\"column-2\">3. De aandrijving deceleratie mechanisme is beschadigd.<\/td><td class=\"column-3\">Verwijder de aandrijving van de klep en draai de hendel. Als het niet kan worden gedraaid, vervang deze met een nieuwe aandrijving.<\/td>\n<\/tr>\n<tr class=\"row-15\">\n\t<td rowspan=\"3\" class=\"column-1\">Positie van het feedback-signaal zonder uitgang<\/td><td class=\"column-2\">1. Onjuiste bedrading schakelaar<\/td><td class=\"column-3\">Controleer of de bedrading correct is volgens het schakelschema van de actor?<\/td>\n<\/tr>\n<tr class=\"row-16\">\n\t<td class=\"column-2\">2. Onjuiste instelling van de volledig op\/fullyoff cam<\/td><td class=\"column-3\">verwijzing<a href=\"\/nl_nl\/faq\/actuator\/set-up-dcl-valve\/\">&#034;Het instellen van een switch-type Elektrische klep&#034;<\/a>Stel de cam positie terecht.<\/td>\n<\/tr>\n<tr class=\"row-17\">\n\t<td class=\"column-2\">3. Overstroom schade veroorzaakt aan de positie terugmelding schakelen.<\/td><td class=\"column-3\">1. verwijzing<a href=\"\/nl_nl\/faq\/actuator\/set-up-dcl-valve\/\">&#034;Het instellen van een switch-type Elektrische klep&#034;<\/a>Controleer of het volledig aan\/fullyoff cam comprimeert u de positie feedback schakelen?<br \/>\n2. Is de meting van de positie feedback loop ingeschakeld?<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<!-- #tablepress-35 from cache --><\/div>\n\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-0c1a5e9 elementor-widget elementor-widget-heading\" data-id=\"0c1a5e9\" data-element_type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<h2 class=\"elementor-heading-title elementor-size-default\">2. Controleer of de toepassing de voorwaarden voldoen de parameter eisen.<\/h2>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-6033e3a elementor-widget elementor-widget-text-editor\" data-id=\"6033e3a\" data-element_type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p>\u00a0 \u00a0 \u00a0 De elektrische aandrijving kan mislukken als gevolg van ondeskundig gebruik of onder de verkeerde voorwaarden van toepassing. Onder de toepassing de voorwaarden die zijn gedefinieerd in de specificatie van het product, de langdurige en probleemloze werking van de aandrijving zal worden gewaarborgd.<\/p><ul><li><strong>Voedingsspanning\uff1a<\/strong>De spanning van de voeding dient te worden binnen de nominale bedrijfsspanning bereik van de aandrijving. Overspanning of onderspanning kan de levensduur van de aandrijving te worden verminderd.<\/li><li><span style=\"font-weight: bold;\">Stroom\uff1a<\/span>Sinds de aanloopstroom van de motor is veel groter dan de nominale stroom. Om te zorgen voor de betrouwbare werking van de aandrijving gebruik van een voeding met een uitgangsstroom capaciteit van meer dan 3 maal de nominale stroom van de aandrijving.<\/li><li><strong>temperatuur\uff1a<\/strong>Zorg ervoor dat de aandrijving actief is binnen het nominale bereik van de bedrijfstemperatuur. Het gebruik van de actuator in een omgeving die groter is dan de nominale operationele temperatuurbereik gebruikt, kan dit leiden tot een slechte actuator-functie of een verminderde levensduur, en uiteindelijk leiden tot het falen van de actuator.<\/li><li><strong>omgeving\uff1a<\/strong>De DCL-schakelaar type aandrijving heeft een IP67-weerbestendig-rating. Over het algemeen geschikt voor binnen of buiten toepassingen. Een zekere mate van regen en spatten bescherming. De bescherming van de aandrijving van regen, sneeuw, ijs en ultraviolet licht (zonlicht) meestal verlengt de levensduur van het product. Zeer corrosieve omgevingen kan leiden tot vroegtijdige uitval van elektronische apparatuur. Gebruik geen niet-explosieveilige serie aandrijvingen in een explosieveilige omgeving.<\/li><li><strong>De Power-on continu\u00efteit snelheid\uff1a<\/strong>De power-continu\u00efteit op het tarief van de DCL schakelactor is 70% (het loopt voor 42 seconden per minuut en moet worden uitgeschakeld voor 18 seconden). Meer dan 70% van de energie-continu\u00efteit op het tarief voor zal zorgen dat de motor in te voeren beveiliging tegen oververhitting.<\/li><\/ul>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-5e6a596 elementor-widget elementor-widget-heading\" data-id=\"5e6a596\" data-element_type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<h2 class=\"elementor-heading-title elementor-size-default\">3. Controleer of de bedrading van de aandrijving correct<\/h2>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<section class=\"elementor-section elementor-inner-section elementor-element elementor-element-21e06a8 elementor-section-full_width elementor-section-height-default elementor-section-height-default\" data-id=\"21e06a8\" data-element_type=\"section\">\n\t\t\t\t\t\t<div class=\"elementor-container elementor-column-gap-default\">\n\t\t\t\t\t<div class=\"elementor-column elementor-col-50 elementor-inner-column elementor-element elementor-element-b9bec88\" data-id=\"b9bec88\" data-element_type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-dcbb3bd elementor-widget elementor-widget-heading\" data-id=\"dcbb3bd\" data-element_type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">Type A: Met een limiet van positie wisselen (contact)<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-8e3675c elementor-widget elementor-widget-image\" data-id=\"8e3675c\" data-element_type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img decoding=\"async\" width=\"400\" height=\"341\" src=\"https:\/\/www.dcl-controls.com\/content\/dam\/actuator\/images\/interface-circuit\/dcl-actuator-interface-diagram-a.webp\" class=\"attachment-full size-full wp-image-4860\" alt=\"DCL \u534e\u6613\u6267\u884c\u5668A\u578b\u63a5\u53e3\u56fe\" srcset=\"https:\/\/www.dcl-controls.com\/content\/dam\/actuator\/images\/interface-circuit\/dcl-actuator-interface-diagram-a.webp 400w, https:\/\/www.dcl-controls.com\/content\/dam\/actuator\/images\/interface-circuit\/dcl-actuator-interface-diagram-a-14x12.webp 14w\" sizes=\"(max-width: 400px) 100vw, 400px\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-a8c8f5f elementor-widget elementor-widget-text-editor\" data-id=\"a8c8f5f\" data-element_type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p>De &#034;aan&#034; en &#034;uit&#034; handelingen kunnen worden gerealiseerd door het switching circuit, en een stel volledig op en volledig off-actieve signalen worden uitgevoerd.<\/p><p><strong>Installatie-instructie\uff1a<\/strong><br \/>1. Terminal 1 is aangesloten op de middelste lijn van de voeding; de<br \/>2. Wanneer de voeding fase en terminal 2 is ingeschakeld, is &#034;off&#034; werking.\uff1b<br \/>3. Wanneer de voeding fase en terminal 3 zijn ingeschakeld, is &#034;op&#034; operatie.\uff1b<br \/>4. Wanneer de voeding fase en terminal 2 is aangesloten en de &#034;off&#034; - operatie wordt in plaats van &#034;full off signaal&#034; - indicator licht verbonden met terminal 4 is op.\uff1b<br \/>5. Wanneer de voeding fase en terminal 3 zijn aangesloten en de &#034;op&#034; operatie in plaats van de &#034;volledig open signaal&#034; lampje aangesloten op klem 5 is op.\uff1b<br \/>6. Terminal 7 massa.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t<div class=\"elementor-column elementor-col-50 elementor-inner-column elementor-element elementor-element-c18850d\" data-id=\"c18850d\" data-element_type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-268e895 elementor-widget elementor-widget-heading\" data-id=\"268e895\" data-element_type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">Type B: Met de intermediaire positie van de schakelaar (passieve contact)<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-69294ea elementor-widget elementor-widget-image\" data-id=\"69294ea\" data-element_type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img decoding=\"async\" width=\"400\" height=\"348\" src=\"https:\/\/www.dcl-controls.com\/content\/dam\/actuator\/images\/interface-circuit\/dcl-actuator-interface-diagram-b.webp\" class=\"attachment-full size-full wp-image-4858\" alt=\"DCL \u534e\u6613\u6267\u884c\u5668B\u578b\u63a5\u53e3\u56fe\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-ad85b91 elementor-widget elementor-widget-text-editor\" data-id=\"ad85b91\" data-element_type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p>De &#034;aan&#034; en &#034;uit&#034; handelingen kunnen worden gerealiseerd door het switching circuit, en een stel volledig op en volledig uit passieve signalen worden uitgevoerd.<\/p><p><strong>Installatie-instructie\uff1a<\/strong><br \/>1. Terminal 1 is aangesloten op de middelste lijn van de voeding; de<br \/>2. Wanneer de voeding fase en terminal 2 is ingeschakeld, is &#034;off&#034; werking.\uff1b<br \/>3. Wanneer de voeding fase en terminal 3 zijn ingeschakeld, is &#034;op&#034; operatie.\uff1b<br \/>4. Terminal 4 is de gemeenschappelijke aansluiting van passieve contacten; de<br \/>5. Wanneer de &#034;open&#034; operatie is in plaats van terminal 5 uitgangen voor een &#034;volledig open signaal&#034;.;<br \/>6. Wanneer &#034;off&#034; is in de plaats, de terminal stelt een &#034;full-uit-signaal&#034;. \uff1b<br \/>7. Terminal 7 massa.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/section>\n\t\t\t\t<section class=\"elementor-section elementor-inner-section elementor-element elementor-element-ebb5092 elementor-section-full_width elementor-section-height-default elementor-section-height-default\" data-id=\"ebb5092\" data-element_type=\"section\">\n\t\t\t\t\t\t<div class=\"elementor-container elementor-column-gap-default\">\n\t\t\t\t\t<div class=\"elementor-column elementor-col-50 elementor-inner-column elementor-element elementor-element-9080197\" data-id=\"9080197\" data-element_type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap elementor-element-populated\">\n\t\t\t\t\t\t<div class=\"elementor-element elementor-element-d3aa831 elementor-widget elementor-widget-heading\" data-id=\"d3aa831\" data-element_type=\"widget\" data-widget_type=\"heading.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t<p class=\"elementor-heading-title elementor-size-default\">Type G: DC regelkring met passieve contact<\/p>\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-3259f4b elementor-widget elementor-widget-image\" data-id=\"3259f4b\" data-element_type=\"widget\" data-widget_type=\"image.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<img loading=\"lazy\" decoding=\"async\" width=\"400\" height=\"391\" src=\"https:\/\/www.dcl-controls.com\/content\/dam\/actuator\/images\/interface-circuit\/dcl-actuator-interface-diagram-g.webp\" class=\"attachment-full size-full wp-image-4853\" alt=\"DCL \u534e\u6613\u6267\u884c\u5668G\u578b\u63a5\u53e3\u56fe\" srcset=\"https:\/\/www.dcl-controls.com\/content\/dam\/actuator\/images\/interface-circuit\/dcl-actuator-interface-diagram-g.webp 400w, https:\/\/www.dcl-controls.com\/content\/dam\/actuator\/images\/interface-circuit\/dcl-actuator-interface-diagram-g-12x12.webp 12w\" sizes=\"(max-width: 400px) 100vw, 400px\" \/>\t\t\t\t\t\t\t\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t<div class=\"elementor-element elementor-element-a7109c8 elementor-widget elementor-widget-text-editor\" data-id=\"a7109c8\" data-element_type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p>Volgens de unidirectionele geleidbaarheid van de diode, door het woon-werkverkeer van de positieve en negatieve elektroden van de DC-voeding, de &#034;on&#034; en &#034;off&#034; activiteiten zijn gerealiseerd en een stel volledig op en volledig uit passieve signalen worden uitgevoerd.<\/p><p><strong>Installatie-instructie\uff1a<\/strong><br \/>1. Terminal 1 is aangesloten op de positieve elektrode van de voeding, en terminal 2 is ingesteld op &#034;off&#034; operatie als deze is aangesloten op de negatieve elektrode van de voeding; terminal 2 is aangesloten op de positieve elektrode van de voeding, en een terminal 1 is &#034;op&#034; operatie als deze is aangesloten op de negatieve elektrode van de voeding.\uff1b<br \/>2. Terminal 3 is de gemeenschappelijke aansluiting van passieve contacten; de<br \/>3. Wanneer de &#034;open&#034; operatie is op zijn plaats, de terminal geeft een &#034;volledig open signaal&#034;.;<br \/>4. Wanneer &#034;off&#034; is in plaats van terminal 5 wordt een &#034;full-uit-signaal&#034;.;<br \/>5. Terminal 7 massa.<\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t<div class=\"elementor-column elementor-col-50 elementor-inner-column elementor-element elementor-element-0934aa3\" data-id=\"0934aa3\" data-element_type=\"column\">\n\t\t\t<div class=\"elementor-widget-wrap\">\n\t\t\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/section>\n\t\t\t\t<div class=\"elementor-element elementor-element-7c9aedd elementor-widget elementor-widget-text-editor\" data-id=\"7c9aedd\" data-element_type=\"widget\" data-widget_type=\"text-editor.default\">\n\t\t\t\t<div class=\"elementor-widget-container\">\n\t\t\t\t\t\t\t\t\t<p><em>Wanneer u een onderzoek op de project site, kunt u contact opnemen met ons bedrijf technical service personeel zo snel mogelijk te onderzoeken wat de fouten en bepalen van de oplossing.<\/em><br \/><em>Telefoonnummer: 13026331611 (Chen Gong)<\/em><\/p>\t\t\t\t\t\t\t\t<\/div>\n\t\t\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/div>\n\t\t\t\t\t<\/div>\n\t\t<\/section>\n\t\t\t\t<\/div>","protected":false},"excerpt":{"rendered":"<p>\u8be5\u5411\u5bfc\u9002\u7528\u4e8eDCL\u8d85\u5c0f\u7cfb\u5217\u7684\u6267\u884c\u5668\uff0c\u578b\u53f7\u5982\u4e0b\uff1a DCL-02A \/ DCL-02B \/ DCL-02G 1\u3001\u5e38 [&hellip;]<\/p>","protected":false},"author":1,"featured_media":5251,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"elementor_theme","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[349],"tags":[374,375,387,34,373],"class_list":["post-6033","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-mr-actuator","tag-dcl-02","tag-dcl-02-on-off","tag-trouble-shooting-guide","tag-actuator","tag-very-small-actuator-tag"],"acf":[],"_links":{"self":[{"href":"https:\/\/www.dcl-controls.com\/nl_nl\/wp-json\/wp\/v2\/posts\/6033","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.dcl-controls.com\/nl_nl\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.dcl-controls.com\/nl_nl\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.dcl-controls.com\/nl_nl\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.dcl-controls.com\/nl_nl\/wp-json\/wp\/v2\/comments?post=6033"}],"version-history":[{"count":0,"href":"https:\/\/www.dcl-controls.com\/nl_nl\/wp-json\/wp\/v2\/posts\/6033\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.dcl-controls.com\/nl_nl\/wp-json\/wp\/v2\/media\/5251"}],"wp:attachment":[{"href":"https:\/\/www.dcl-controls.com\/nl_nl\/wp-json\/wp\/v2\/media?parent=6033"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.dcl-controls.com\/nl_nl\/wp-json\/wp\/v2\/categories?post=6033"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.dcl-controls.com\/nl_nl\/wp-json\/wp\/v2\/tags?post=6033"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}